Traction current converter plant
Woburn rail traction substation in Lower Hutt, New Zealand, supplying 1500 V DC to the electrified Hutt Valley Line.
Cos Cob Anchor Bridge Substation on the New Haven Line in Connecticut, U.S.

A traction substation, traction current converter plant, rectifier station or traction power substation (TPSS) is an electrical substation that converts electric power from the form provided by the electrical power industry or railway owned traction power network to an appropriate voltage, current type and frequency to supply trains, trams (streetcars) or trolleybuses with traction current. A traction power substation may also refer to a site that supplies a railway traction power network with power from the public electricity utility.

Function

[edit]

The exact functions and power conversions made by a traction substation depends on the type of electrification system in use. Broadly there are three categories of electrification system each with different system architectures.

Low voltage DC systems were the first kind of electrification to emerge in the late 1800s using both overhead line and conductor rail collection. Although many countries (especially in Japan and across Europe) implemented 1.5kV or 3kV DC overhead line networks across mixed traffic mainline networks, the system is mostly deployed nowadays on rapid transit, or short distance/high frequency suburban systems as well as light rail, trams and trolleybuses. 750V is the standard for metros using conductor rail collection and tram or light rail (using overhead line) while 1.5kV is the standard for metros and commuter systems using overhead line collection.

The main benefit of these systems is the relative lack of on-board conversion equipment required by the train with it possible to connect the traction current directly to the traction motor control equipment. This is opposed to AC electrification which requires voltage transformation and (typically) rectification on board every train. However, the lower line voltage means a greater number of tractions substations must be built with the DC current needing to be supported at regular intervals of between 2 and 12 km depending on exact system voltage and traffic levels/line speed. Although a higher line voltage would decrease the number of substations needed, the maximum traction voltage of a DC system is limited by

  1. the physical size on-board traction motors can be (higher voltages require larger insulation components)
  2. the expense and complexity of rectification equipment for higher voltages (especially historically speaking)
  3. the difficulty in breaking DC fault currents
  4. the requirement to use conductor rail electrification which limits voltage to a maximum of 1200V due to insulation requirements

The frequent substation spacing and relative lack of on-train equipment required means low-voltage DC system see regular use on short distance/high frequency railways (like metros) because the number of trains running will be greater than the number of transformers and rectifiers installed in traction substations when route distances are short and train frequencies high.

Architecture[1]

[edit]

This need for many regular DC supply points means low voltage DC systems are likely to utilise a high voltage 3 phase AC traction power network, although this isn't always the case. Broadly speaking, DC electrification that uses traction power networks are typically larger metros and suburban networks started in the early 20th century when public electricity infrastructure was not as readily available (since DC electrification dates back to the late 19th century). While DC electrification installations that connect to the public utility grid at every traction substation were typically installed more recently or are tram systems since public electricity infrastructure is most dense in urban areas.

Traction power networks for DC electrification utilise high voltage 3 phase AC current at utility frequency (50 or 50 Hz) and at common voltages of 11, 22, 33 or 66kV although lower voltages have been used historically. 50–60 Hz 3-phase AC is not only used for its efficient power transmission properties but also for easy integration with the local electricity grid made possible by the fact that AC/DC rectifiers can easily be fed with 3-phase AC. The railway traction power network primarily supports multiple DC Traction Substations (TSS) where the current is converted to low voltage DC for the railway electrification system. Trains then collect the low voltage DC current which can be fed directly to a motor control system, either resistor banks for DC motors or an inverter motor drive for 3 phase AC motors.

Types of substation

[edit]
Grid Supply Point (GSP)
[edit]

This is a substation where the railway's traction power network is supplied by the local electricity grid. Since traction power networks for DC railways can be three-phase and can be rated at voltage levels similar to that of the electricity grid in that jurisdiction, grid supply points are often simply switching stations where incoming grid circuits are collected to a busbar and then distributed on the railway side. Or, if the railway load is especially high, the electricity supplier can provide dedicated transformers for railway use supporting the railway traction power network from a higher grid voltage (like ~132kV). Typically, the supplies from different grid supply points are kept separated within the traction power network by using normally open circuit breakers. This is done to limit the impact of a HV fault and to ensure the correct load is being drawn from each grid supply point to avoid over currents (each grid site in a railway system is normally rated for a different power draw).

Traction Substation (TSS)
[edit]

This is where the high voltage 3-phase AC of the traction power network is first stepped down to the traction current voltage (600–3000V) using a power transformer then rectified to DC before being distributed to the immediate overhead line or conductor rail circuits. The AC switchboard of a typical DC traction substation normally connects to multiple AC circuits allowing for the substation to be fed from two different points for resiliency, and the ability to move the normally open point between different grid supplies around the traction power network. It may also support other auxiliary transformers to supply railway signalling systems, tunnel drainage pumps or station domestic supplies. Where a traction power grid is not used, the three-phase voltage from the local utility is stepped down and rectified in the traction substations to provide the required DC voltage. The typical physical spacing of DC traction substations depends primarily on the traction power voltage supplied to the trains but also the traffic demand and average line speed.

DC Substation Spacing[2]
DC Electrification Voltage Spacing of Traction Substations (TSS)
600V 2–3 km
750V ~3 km
1500V 2–8 km
3000V 7.5–12.5 km
Track Paralleling Hut (TPH)
[edit]

The distance between traction substations can be increased by installing one or more track paralleling huts between adjacent traction substations. A track paralleling hut provides means for each overhead line or conductor rail circuit to be electrically paralleled at a shared DC busbar. This allows for more efficient use of available power by connecting more trains in parallel to supply points reducing volt drop.

Tee'd Substation
[edit]

This is similar to a TSS but refers to a situation where the DC substation has no ability to switch high voltage AC circuits and is permanently attached to a particular circuit of the traction power network as opposed to a normal traction substation which can switch AC circuits to some extent. Tee'd substations have less operational resiliency than normal TSSs but save in installation and operational cost since no AC switchboard is built other than a single circuit breaker. Track Paralleling Huts are often converted into tee'd substations as a cost effective way to increase the available power to a railway line.

12–15kV AC overhead line

[edit]

Higher voltage AC electrification at low frequency is almost as old as low voltage DC systems being implemented as early as 1904. Originally, the low frequency AC system fundamentally relied on the utilisation of universal motors with AC current of a frequency between 16 and 25 Hz. In the early 1900s, the technology did not exist to implement rectifiers or power electronics on board trains so engineers were limited in methods to run traction motors. Higher frequencies (like those which came to be used by the electrical supply frequency) were found to create intolerable arcing between motor components but at lower frequencies these problems were resolved. This allowed for trains to be fed at a high line voltage which can be then stepped down by an onboard transformer to a voltage appropriate for a traction motor, then fed directly as AC to the motors. Almost all AC systems that have been implemented at scale use single-phase AC due to the mechanical and practical complexities of duplicating catenary systems as is required by 3-phase AC electrification

In the early years of railway electrification, the main advantage of low frequency AC systems was that AC can be fed to trains at a much higher voltage than that which is optimal for the traction motors since the AC voltage can be stepped down on board the train rather than matching exactly what is required by the traction motor (like on DC electrification since DC cannot be stepped up or down). This leads to several further advantages of an AC electrification system

  1. Line voltage can be set much higher allowing for far fewer substations to be built as high voltage transmission of electricity is more efficient over distance.
  2. The higher line voltage can allow for much more power to be delivered to trains allowing for high speed rail and heavy freight traffic
  3. Higher line voltage means catenary wires can be thinner reducing material cost not only from the thinner wiring but also the reduced weight of overhead line support structures since they are now supporting a lighter installation.

AC electrification and low frequency became the standard system for suburban, mixed traffic and high speed lines in Germany, Austria and Switzerland at 15kV 16.7 Hz; Sweden and Norway at 15kV 16+23; and some parts of Northeast USA at 12kV 25 Hz. Historically, line voltages of between 6.6kV and 11kV were implemented.

Architecture

[edit]

What came to be the main disadvantage of low frequency AC electrification was that it required single phase AC power at a specific non-standard frequency (between 16.667 and 25 Hz). Both low frequency AC and low voltage DC systems originally needed to implement their own traction power networks and power generation stations fundamentally because national utility grids did not exist in the early 1900s. However, as the general purpose electrical supply grids grew in size and scope throughout the 20th century, they standardised on 3-phase AC transmission at 50 or 60Hz. Low voltage DC systems could easily integrate their traction power networks with the electrical supply industry since they would have already been 3-phase and did not require a specific frequency allowing DC railways to generally forgo the need for traction power stations. However, low frequency AC systems became non-standard and incompatible with electrical supply industry at large due to being single phase and a different frequency. Interactions between low frequency AC electrification and national power grids therefore require complex and expensive machinery (and later power electronics) to convert three-phase 50 Hz or 60 Hz alternating current (AC) for the supply of AC railway electrification systems at a lower frequency and single phase.

Similarly to DC systems, low frequency AC systems may utilise a traction power network at voltages of between 55kV and 138kV to support overhead line voltages of either 12kV or 15kV. Unlike DC systems though, these traction power networks are necessarily single phase and low frequency. Furthermore, some low frequency AC installations (such as in Norway, parts of Sweden and north-east Germany) are decentralised meaning overhead line traction substations connect directly to the electrical supply industry with each of these substations requiring individual frequency and phase conversion equipment.

For administrations that use centralised traction power networks, the distribution voltage is 55kV is some parts of Austria, 66kV in some parts of Switzerland,110kV in Germany and most of Austria, 132kV in most of Switzerland and Sweden, and 138kV on the southern section of the Northeast Corridor in the USA. In either centralised or decentralised systems, it's common for the traction power network and the relevant overhead line electrification to utilise autotransformer feeding (sometimes referred to as balanced line transmission) meaning that a 15kV railway is actually fed by a 30kV transformer with +15kV connected to the contact wire, a centre tap earthed to the running rails, and -15kV connected to external feed wires. At points between railway substations, the negative feed wires are connected to the positive contact wires by autotransformers in order to allow a greater current in the contact wire. Similarly, a 110kV transmission line is in fact made up of three wires at +55kV, 0V and -55kV making 110kV in total between all conductors.

Either way, 12kV or 15kV AC is collected by trains and stepped down by an on-board transformer to a voltage appropriate to traction motors. In newer trains, it may also be rectified to DC in order to feed a 3-phase traction motors via a motor drive.

Substations

[edit]
Centralised Converter Station
[edit]

These substations convert between 3-phase 50 Hz or 60 Hz power from the electrical supply industry to single phase low frequency power for use in a high voltage (55kV—138kV) traction power network. They may also directly supply the 12kV–15kV overhead line locally if the substation is near to a railway line. Converter stations may utilise motor-generator machinery or solid state power electronics.

Traction Substation
[edit]

In the context of a railway traction power network with traction power stations or centralised converter stations, this refers to a site where the traction power network feeds a stepdown transformer to feed overhead lines at either 12kV or 15kV depending on country.

Decentralised Converter Station
[edit]

This refers to a site where 3 phase 50 or 60 Hz power is provided by the electrical supply industry and converted to single phase low frequency AC and transformed directly to traction current voltage to be supplied to overhead lines local to that substation

Autotransformer Site
[edit]

These substations occur at the 12-15kV level at the overhead line equipment and serve to connect negative feed wires to contact wires via autotransformers in order to increase the possible distance between supplying substations. These are not actually unique to low frequency AC systems and can be found on mains frequency AC railways (see below) that utilise autotransformer feeding.

25kV AC (50Hz or 60Hz) Overhead Line

[edit]

This is the most common type of electrification for modern mixed traffic, long distance and high speed railways and sees use around the world. Often considered the modern-day standard, it only became available from the late 1950s and so is often seen in countries whose railway networks started electrifying later. Some administrations use alternate voltages of 20kV or 12.5kV but the system is functionality the same.

The use of alternating current of 50 or 60 Hz indicates that the system directly connects the local electricity grid to the overhead line circuits giving the system the simplest architecture requiring no complex frequency or current conversion equipment at substations and are always decentralised requiring no traction power network. However, it requires more on-board train equipment typically transformers and rectifiers to convert the current to a lower DC voltage (typically around 800V) in order to power DC motors or 3 phase AC motors via an inverter motor drive.

Equipment

[edit]
Traction substation in Loopealse, Tallinn, Estonia

Rotating

[edit]

Originally, the conversion equipment usually consisted of one or more motor-generator sets containing three-phase synchronous AC motors and single-phase AC generators, mechanically coupled to a common shaft. Rotary converters were also used, especially where the desired output was DC current from an AC source.

Static

[edit]

In the 1920s, DC was derived using electronic valves (mercury arc rectifiers). In modern systems, high-voltage DC (HVDC) "back-to-back" stations are used instead of mechanical equipment to convert between different frequencies and phases of AC power and solid-state thyristor rectifier systems are used for conversion from AC power to DC traction power.

Location

[edit]

Traction current converter plants are either decentralized (where one plant directly supplies the overhead lines or third rail of the traction system, with no feed into a traction current distribution network) or centralized (for the supply of the traction power network, usually in addition to the direct supply of the overhead lines or third rail).

Central traction current converter plants are generally found in Germany (primarily in the cities of Neckarwestheim, Ulm, Nuremberg), Austria and Switzerland, while decentralized traction current converter plants are generally found in Norway, Sweden and the German states of Mecklenburg-Vorpommern and Brandenburg as well as parts of Great Britain. A List of railway electrification systems provides further detail.